Task: | Adjust |
---|---|
Structure: | Combination |
Mathematical Model: | Linear |
Signal: | 4-20ma HART RTD |
Function: | Automatic Control, Protection, Monitoring, Measurement |
Certification: | ISO: 9001, CE, CMMI5 |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Communication parameters | Module consumption | ||||
Number of communication ports | 1 (Can communicate with 6 MODBUS TCP master station at the same time) | Extension Bus power supply (5VDC) |
120mA
|
||
Extension Bus power supply (24VDC) |
20mA
|
||||
Type of interface | |||||
Ethernet (RJ45) | |||||
Communicate protocal | MODBUS TCP slave station Port : 502 |
Dimensions and Mounting | |||
Configure the content | IP address; Subnet mask; Gateway IP; MAC address; |
Dimensions | 72mm(L) X 80mm(W) X 63mm(H) | ||
Weight | 160g | ||||
Way to install | 35mm DIN rail | ||||
Panel mounting type | |||||
Work Environment | |||||
Communication rate |
10/100Mbps
|
Operating temperature | 0 ~ +55ºC | ||
I/O area |
Input 100KB
Output 100KB |
Storage temperature | -40 ~ +70ºC | ||
Relative humnidity | 5% ~ 95% Noncondensing | ||||
Maximum number of sites per network | According to configuration software |
Function code | Function (Master station) |
01 | Read switch output status |
02 | Read switch intput status |
03 |
Read analog output status
|
04
|
Read analog input status |
05
|
Forces the output value of a switch |
06
|
Forces the output value of analog |
15
|
Forces the output value of multiple switches to be set |
16
|
Forces the value of multiple analog outputs to be set |
DATA AREA | TYPE | ADDRESS RANGE | MODBUS ADDRESS | MAPPING FORMULA | MODBUS DATA TYPE |
|
Zone I |
%IX
|
BOOL
|
%IX2.0~%IX201.7
|
0~1599
|
IXm.n: (m- first address) *8+n
|
0x
|
%IW
|
WORD
|
%IW2~%IW200
|
0~99
|
IWm:(m - first address)/2
|
4x
|
|
Zone Q |
%QX
|
BOOL
|
%QX2.0~%QX201.7
|
0~1599
|
QXm.n:(m - first address) *8+n
|
1x
|
%QW
|
WORD
|
%QW2~%QW200
|
0~99
|
QWm:(m - first address)/2
|
3x
|
Suppliers with verified business licenses