• CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out
  • CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out
  • CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out
  • CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out

CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out

Task: Adjust
Structure: Combination
Mathematical Model: Linear
Signal: Continuous
Function: Protection
Certification: RoHS, CCC, ISO: 9001, CE
Samples:
US$ 50/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2020

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
CB4071-EX
Condition
New
Customized
Customized
Material
Plastic
Input Signal
Thermal resistance PT100
Power Supply Mode
24VDC
Power Connection Mode
Terminal Power Supply
Transport Package
Standard Export Package
Specification
114.5*99*12.5mm
Trademark
CHNT
Origin
China
HS Code
8536300000
Production Capacity
5000pieces/Week

Product Description

CHINT RTD,Isolated Barrier(1 channel) 1in and 1out
RTD Input Isolated Barrier,Isolation from hazardous areas to safe areas, The product requires independent power supply, power supply, input and output three isolation.

CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out

Production parameters
 
MODEL NO CB4071-EX
Number of channel 1 input/1 output
Supply voltage(Ue) 20~35V DC
Input signal Pt100;Cu50;Cu100
Output signal 0~20mA;4~20mA;0~5V;1~5V
Ex-marking [Ex ia Ga]IIC
Field apparatus 2-RTD;3-wire RTD

CHINT RTD signal isolator and barrier 1 channel 1 in and 1 outCHINT RTD signal isolator and barrier 1 channel 1 in and 1 out
CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out
Technical data
 
1. General
Number of channels 1input/1output 
Dielectric strength Non-intrinsically safe part and intrinsically safe part≥2500VAC,power supply part and non-intrinsically safe part≥500VAC
Temperature drift 0.01%F.S./ºC
Response time Reach 90% of final value in 1s
Insulation resistance Non-intrinsically safe part and intrinsically safe part≥100MΩ,power supply part and non-intrinsically safe part≥100MΩ
Electromagnetic compatibility According to IEC 61326-1(GB/T 18268)
EX marking [Ex ia Ga]IIC [Ex iaD]
Weight Approx 100g
Field apparatus 2-wire RTD;3-wire RTD
Suitable location zone 0;zone 1;zone 2;IIA;IIB;IIC;T4~T6


2. Input Data 
Input signal Pt100;Cu50;Cu100

3. Output Data 
Output signal 0~20mA;4~20mA;0~5V;1~5V
Current output load resistance  RL≤300Ω
Voltage output load resistance  RL≥20kΩ
Alarm indication Lower than range, LED L falshing, output current ≈3.8mA;Higher than range, LED H falshing, output current ≈20.8mA;Breakage, LED L and H falshing at the same time, output current ≈20.8mA;Short circuit, LED L and H falshing alternately, output current ≈3mA

4. Power Supply
Supply voltage(Ue) 20~35V DC
Power protection Reverse protection of power supply
Current consumption ≤65mA (at 24Vdc supply,20mA output)
Power supply mode Independent power supply
Power connecting mode Terminal

5. Housing
 
Material PA
Degree of protection IP20
Flammability rating UL94/V0
Colour grey

6. Product approvals
 
Approvals NEPSI


7. Standard/Specification
NEPSI [Ex ia Ga] IIC Comply with standard: GB 3836.1,GB 3836.4,GB 3836.20 [Ex iaD] Comply with standard: GB 12476.1,GB 12476.4


8. Safe data 
Max. r.m.s. a.c. or d.c. voltage Um 250V
Max.output voltage Uo 28V(7,8,9)
Max.output current Io 93mA(7,8,9)
Max.output power Po 651mW(7,8,9)
IIC Max. external inductance Lo 4.2mH(7,8,9)
IIC Max. external capacitance Co 0.083μF(7,8,9)
IIB Max. external inductance Lo 12.6mH(7,8,9)
IIB Max. external capacitance Co 0.65μF (7,8,9)
IIA Max. external inductance Lo 33.6mH(7,8,9)
IIA Max. external capacitance Co 2.15μF(7,8,9)

9. EMC DATA 
Electrical fast transient/burst immunity According to:IEC 61326-1;Class A
Surge immunity According to:IEC 61326-1;Class B
Radiated,radio-frequency,electromagnetic field immunity According to:IEC 61326-1
Electrostatic discharge immunity According to:IEC 61326-1;Class A
Immunity to conducted disturbances, induced by radio-frequency fields According to:IEC 61326-1


10. Operating Conditions
Ambient temperature -20ºC~+60ºC
Storage temperature -40ºC~+80ºC
Relative humidity 10%~90%
Environmental requirements The air should not contain any medium corrupting the coat of chrome,nickel and silver.Moreover,violent quiver and impact or any cause of electromagnetic induction (such as big current or spark,etc.)must be avoided when using


11. Connection Data
Conductor cross section solid range 0.5~2.5mm²
Conductor cross section flexible range 0.5~2.5mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 24
Stripping length 8mm
Screw thread M3
Connection method Screw connection
Tightening torque min. 0.5 Nm
Tightening torque max. 0.6 Nm


12. Installation
Mounting type DIN35mm


 


CHINT RTD signal isolator and barrier 1 channel 1 in and 1 out

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2020

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
291
Year of Establishment
2005-09-01